1.1
Plan and Space Design
|
28
|
1.1.1.
Plan Function Assemblage
|
1
Include basic program requirements, i.e. bathroom,
kitchen, living room, bedroom, storage
2
Divide Public and Private within the unit
3
Well-designed circulation
4
Close proximity of Living Room, Dining Room and Kitchen
5
Set up threshold/transition space between public and
private
6
Set up reading room in each unit
|
7
|
2
1.2
1
1.2
1
.6
|
|
1.1.2
Space Functionality
|
1
Reasonable assignment of Main Rooms
2
Master Bedroom > than 14 sm, and has master bathroom.
Other bedrooms > 9sm
3
Living Room > 18sm, Continuous wall space > 3m
long, short length of LR > 3.9 m
4
LR and Bedrooms have good views
5
Dining Room > 10sm, and has natural ventilation
and lighting
6
Master Balcony depth > 1.5 m. Second balcony >1.2m.
7
Storage space > 2 cubic meters
|
7
|
2
1
2
.5
.5
.5
.5
|
|
1.1.3
Kitchens and Bathrooms
|
1
Kitchen > 6 sm
2
Single Bathroom Unit - Bathroom area > 4.5 sm. Two
Bathroom Unit Bathrooms > 7sm.
3
Kitchen should be close to entrance and has natural
light and ventilation
4
Kitchen usable area length > 2.7 m and width >
1.8 m.
5
n/a
6
Apts with 3+ bedrooms should include 2 bathrooms, one
for MB
7
n/a
8
Bathroom should be close to the bedrooms. If the design
has several bathrooms, one is for public, one private
|
5
|
.8
.8
.5
.6
.6
.5
.7
.5
|
|
1.1.4
Area and Space Using Ratios
|
1
High-rise buildings > 72% used area coefficient.
Mid-rise > 78% used area coefficient.
2
Length to Width Ratio < 2
3
Circulation Area < 5% of total unit area
4
Height > 2.5 m, Some special space can be 2.1
5
Kitchen > 2.2 m
6
Bathroom > 2.2 m
7
n/a
|
4.5
|
1.2
1
.6
.4
.4
.4
.4
|
|
1.1.5
level changes
|
1
Level change in apt < 20mm
2
Entrance width > 1m
3
Kitchen and Bathroom width > 0.8 m
4
Ramp slope angle < 1/10
|
1.5
|
.4
.4
.4
.3
|
|
1.1.6
Public Areas
|
1
n/a
2
width of stairs > 1.2 sm, step riser = 175 mm, stair
tread = 260mm
3
n/a
4
Hall for first story for all units. for multi-stories,
hall > 6sm. For high-rise, hall > 15 sm.
5
n/a
|
3
|
.5
.7
.7
.6
.5
|
|
1.2
Equipment setup
|
15
|
1.2.1
Decoration
|
n/a
|
3
|
|
|
1.2.2
for kitchens and bathrooms
|
n/a
|
3.5
|
|
|
1.2.3
heating and cooling
|
n/a
|
1
|
|
|
1.2.4
pipes and wires
|
n/a
|
3
|
|
|
1.2.5
electrical power, communication
|
n/a
|
1.5
|
|
|
1.2.6
water, electric, gas meters
|
n/a
|
1.5
|
|
|
1.2.7
connections
|
n/a
|
1.5
|
|
|
1.3
flexibility, transform-ability
|
12
|
1.3.1
construction system
|
1
open space > 6.6m
2
light and movable partitions
3
convenient organization of walls, columns, and beams
|
5
|
2
1.2
1.8
|
|
1.3.2
architectural mode
|
1
unit plan designs sizes satisfy mode cooperative principle
2
kitchen and bathroom use mode cooperative size
3
n/a
|
3
|
1.2
1
.8
|
|
1.3.3
changeable parts of equipments
|
1
Standard doors and windows
2
n/a
3
n/a
|
4
|
1.5
1.5
1
|
|
1.4
Insulation
|
15
|
1.4.1
Insulation
|
Insulation factor must follow the following requirements:
Q = local energy saving design standards
For cold areas
- wall K £ 0.9Q (K = heat transfer
coefficient)
- roof - K £ 0.9Q
- window K £ 0.9Q
- balcony and unit entrance door K £
0.9Q
- floor K £ 0.9Q
- stair wall K £ 0.9Q
- room door K £ 0.9Q
For seasonal areas hot summer and cold winter
- wall K £ 1.5 W/m2K (K
= heat transfer coefficient)
- wall (heat indolent) - K ≥ 3.2
- roof K £ 1.0 W/m2K
- roof (heat indolent) K ≥ 3.2
- window, balcony door K £ 1.0 W/m2K
- window shading
For mild areas (Shenzhen)
- wall K £ 2.2 W/m2K (K
= heat transfer coefficient)
- wall (heat indolent) - K ≥ 3.2
- roof K £ 1.5 W/m2K
- roof (heat indolent) K ≥ 3.2
- window, balcony door K £ 4.5 W/m2K
- window shading
|
13
|
4.5
1
4
1
1
1
.5
4.5
1
2.5
1
3
1
4.5
1
2.5
1
3
1
|
|
1.4.2
Leakage
|
n/a
|
2
|
|
|
1.5
Indoor Noise Protection
|
14
|
1.5.1
noise protection for walls
|
1
party walls between units protection > 45
db
2
interior unit wall protection > 30 db
3
unit entrance door protection > 30 db
4
wall with window protection > 35 db
|
6
|
2
1.5
1
1.5
|
|
1.5.2
roof and floor slabs
|
1
floor protection from actions i.e. hitting floor
etc. < 70db
2
interior floor slab protection > 45 db
|
4
|
2.5
1.5
|
|
1.5.3
natural noise
|
1
interior unit noise during daytime < 50 db
2
interior unit noise during nighttime < 40 db
|
2
|
1
1
|
|
1.5.4
equipment noise
|
1
noise from bathroom equipments < 55 db
2
noise from exhaust equipment < 60 db
3
noise from water pipes < 45 db
|
2
|
.7
.6
.7
|
|
1.6
Lighting
|
|
1.6.1
natural lighting
|
1
Window to floor area ratio > 1 / 7
2
Distance between buildings should satisfy the Sunshine
Law.
3
At least one bedroom should get direct sunlight exposure.
If the apt has 4+ bedrooms, then two bedrooms should have
direct sun exposure.
4
Bedroom should have no obvious shading
|
3
|
1
.7
.7
.6
|
|
1.6.2
artificial lighting
|
n/a
|
1.5
|
1
.5
|
|
1.6.3
natural and artificial lighting for public areas
|
1
n/a
2
Window to floor area ratio > 1 / 7
3
n/a
|
1.5
|
.7
.5
.3
|
|
1.7
Ventilation
|
|
1.7.1
indoor ventilation
|
1
natural ventilation
2
mechanical ventilation in kitchens and bathrooms
|
2
|
1
1
|
|
1.7.2
exhaust
|
1
set up horizontal or vertical exhaust in kitchen
2
n/a
3
n/a
|
2.5
|
1.2
.8
.5
|
|
1.7.3
equipment
|
1
n/a
2
n/a
|
1.5
|
.5
1
|
|
1.8
Energy Savings
|
|
1.8.1
application of energy saving system
|
1
at least two new introduced technologies
2
energy saving windows
3
indoor adjustable temperature
|
2
|
.7
.7
.6
|
|
1.8.2
water
|
1
special toilets
2
|
1
|
1
|
|
1.8.3
lighting
|
1 public lighting using energy saving control systems
|
.5
|
.5
|
|
1.8.4
new resources
|
1 solar energy, ground heat pumps, wind energy
|
.5
|
.5
|
The above is a checklist to evaluate technical requirements specified
by Chinas National Standard for residential Class - used to
evaluate designs for the National Award for Health and Comfort Residential
Project.