|
Technical Recommendations
for Shenzhen Wonderland
6/28/2000
Sephir.
D. Hamilton, Brian. Dean
Introduction to the Project
The conceptual design for the B1 and C1 sites
on the Wonderland development in Shenzhen, China is complete. From
the site layout to the window details, architects and engineers
manipulated the design to produce a sustainable housing development.
Designers considered the site, its surroundings, and the local climate
to create the design, which works with nature to produce energy-efficient
and comfortable apartments for the people of China. This report
details the overall technical considerations that guided the design.
Based on technical analysis using DOE-2
software, Phoenics CFD software, and sound engineering knowledge,
the Building Technology team at the Massachusetts Institute of Technology
makes several design recommendations in this report. The submitted
architectural design reflects many of the recommendations, while
others need further attention during the design and construction
process. If all recommendations are implemented, we predict energy
savings of up to ~2000 kWh (~60%) annually compared to the currently
constructed apartments. First, this report
presents a summary of recommendations in two tables. The table
ranks each recommendation with one, two, or three stars depending
on its importance to the sustainability of the design. Some items
that have only one or two stars are still important, especially
to occupant comfort during the hottest months, though they may not
be essential to the annual energy use.
Next, the report demonstrates the possible
energy savings of the recommendations. It shows the effect of implementing
all the three-star items, all the three and two-star items, and
all the items together.
Finally, the report details the technical aspects
of the design. It explains the logic behind the building orientation
and layout; it describes each side of the building façade (including
the roof); it shows the possibilities of natural and fan-assisted
ventilation; it reiterates the importance of reducing train noise;
and then it discusses the programmable thermostat and air-conditioning
units.
Summary of Recommendations
Apartments primarily facing North and
South
|
Building Design Features
|
| |
|
Windows
|
North
|
Overhang: 10 % of window height;
Fin: 10% of window width;
Solar Heat Gain Coefficient < 0.8
Clear single-pane window; (vinyl frame if possible)
|
|
|
South
|
Overhang: 20% of window height;
Fin: 10 % of window width;
Solar Heat Gain Coefficient < 0.8
Clear single-pane window; (vinyl frame if possible)
|
|
|
Noise Control
|
Tightly sealed windows (double-pane, non-operable if possible)
on walls adjacent to railroad.
|
|
| |
|
Walls
|
Insulation
|
Block wall plus 6 cm. (R=1.5 or greater) of insulation on
west facing exterior walls.
|
*
|
|
Noise Control
|
Increase mass of walls adjacent to railroad by filling block
wall cavities with dense concrete.
|
**
|
| |
|
Infiltration
|
Blower door test (Random sample units)
|
Less than 0.35 air changes per hour (fresh air by natural
or mechanical ventilation). All joints and cracks should
be sealed well.
|
***
|
| |
|
Roof
|
Insulation
|
Have at least 14 cm. (R-3.67) of typical fiberglass insulation
or comparable insulation rating inside weather barrier. This
will keep the top floor units from being too hot in the summer.
|
***
|
| |
|
Door
|
Noise Control
|
Exterior door adjacent to railroad should be heavy, such
as metal with foam core or solid wood and should have gaskets
and weather stripping to minimize infiltration of air or noise.
|
**
|
| |
|
Building Equipment Features
|
| |
|
Cooling
|
Air Conditioning
|
3 COP minimum, plus 0.3 COP each time the upgrade costs less
than 1500 yuan. (example: add 0.9 COP [3.9 COP total] if cost
of upgrade is less than 4500 yuan; add 1.2 COP if < 6000
yuan)
|
HH
|
| |
|
Ventilation
|
Off peak ventilation
|
Closable through-wall exhaust fan (ensure that they are properly sealed to have
minimal infiltration when ventilation is not in use).
For top floor units the exhaust fan should be placed
near the roof.
|
HHH
|
| |
|
Thermostat
|
Programmable Digital Clock Thermostat
|
Install a programmable digital clock thermostat that controls
the air-conditioner. Install a thermostat that reads indoor
and outdoor temperatures.
|
HHH
|
| |
|
Hot Water
|
Solar Collector
|
Significant energy can be collected from the sun to heat
the water used for bathing and washing.
|
H
|
| |
|
HHH Essential for Sustainability HHRecommended
Feature HAdditional Feature
|
Apartments
primarily facing East and West
|
Building Design Features
|
| |
|
Windows
|
East and West with overhang
|
Overhang: 100 % of window height;
Fin: 0% of window width;
Solar Heat Gain Coefficient < 0.8
Clear single-pane window; (vinyl frame if possible)
|
***
|
|
East and West no overhang
|
Overhang: 0% of window height;
Fin: 0 % of window width;
Solar Heat Gain Coefficient < 0.4
See window specification sheet for window types.
|
|
Noise Control
|
|
**
|
| |
|
Walls
|
Insulation
|
Block wall plus 6 cm. (R=1.5 or greater) of insulation
on west facing exterior walls.
|
*
|
|
Noise Control
|
Increase mass of walls adjacent to railroad by filling
block wall cavities with dense concrete.
|
**
|
| |
|
Infiltration
|
Blower door test (Random sample units)
|
Less than 0.35 air changes per hour (fresh air by natural
or mechanical ventilation). All joints and cracks should
be sealed well.
|
***
|
| |
|
Roof
|
Insulation
|
Have at least 14 cm. (R-3.67) of typical fiberglass insulation
or comparable insulation rating inside weather barrier.
This will keep the top floor units from being too hot in
the summer.
|
***
|
| |
|
Door
|
Noise Control
|
Exterior door adjacent to railroad should be heavy, such
as metal with foam core or solid wood and should have gaskets
and weather stripping to minimize infiltration of air or
noise.
|
**
|
| |
|
Building Equipment Features
|
| |
|
Cooling
|
Air Conditioning
|
3 COP minimum, plus 0.3 COP each time the upgrade costs
less than 1500 yuan. (example: add 0.9 COP [3.9 COP total]
if cost of upgrade is less than 4500 yuan; add 1.2 COP if
< 6000 yuan)
|
**
|
| |
|
Ventilation
|
Off peak ventilation
|
Closable through-wall exhaust fan (ensure that they are properly sealed to have
minimal infiltration when ventilation is not in use).
For top floor units the exhaust fan should be placed
near the roof.
|
***
|
| |
|
Thermostat
|
Programmable Digital Clock Thermostat
|
Install a programmable digital clock thermostat that controls
the air-conditioner. Install a thermostat that reads indoor
and outdoor temperatures.
|
***
|
| |
|
Hot Water
|
Solar Collector
|
Significant energy can be collected from the sun to heat
the water used for bathing and washing.
|
*
|
| |
|
***Essential for Sustainability **Recommended
Feature *Additional Feature
|
Total Energy Savings
Compared with a base-case,
the suggestions summarized above will save up to ~60% in annual
energy use.
| Building Component
|
Description
|
|
Floor area
|
1 story, 6m x 12m
|
|
Orientation
|
Primarily north/south facing facades
|
|
Wall type
|
Concrete block, no insulation
|
|
Window type
|
Clear single pane, aluminum frame
|
|
Window area
|
40% window to wall area
|
|
Overhang type
|
None
|
|
Electric Air Conditioner
|
3 COP
|
|
Heating Setpoint
|
20 degrees Celcius
|
Cooling Setpoint
|
24 degrees Celcius
|
|
Ventilation
|
None
|
Base Case
Possible Savings
| |
KWh (annually)
|
% savings
|
|
Base Case
|
4500 - 5200
|
--
|
|
3 Star Recommendations
|
~2700
|
40-50%
|
|
1, 2, & 3 Star
|
1500-1800
|
60-70%
|
Building Orientation and Layout
Buildings are oriented to minimize
east/west exposure
Solar gain through windows accounts for approximately
40% of the total cooling energy load for a Base Case apartment in
Shenzhen (Base Case is defined above). Over a year,
the energy from direct sunlight per area incident on all building
surfaces (north, south, east, and west) totals nearly 2.53 MWh/m2.
Western and eastern facing windows each see 32% (64% combined) of
the total annual solar energy per area. Southern windows see 33%
and northern windows see 3%. Obviously, then, all energy-efficient
designs in Shenzhen should try to minimize western and eastern exposures.
Northern row of buildings is continuous to
block train noise

Trains produce approximately 90dBA of noise.
When people open windows, go onto balconies, or walk in courtyards
they expect that noise is no greater than 45dBA. The northern row
of buildings cannot avoid the train sounds, but can block the rest
of the site. No openings should exist between the courtyard and
the train tracks through the northern row of buildings. Even small
openings in the northern row of buildings, such as a narrow walkway,
will greatly increase the noise levels in the courtyard.
Eastern side of the site is open to allow wind
movement through the site
Wind should flow freely through courtyards,
balconies, and apartment in order to keep people comfortable during
hot months and to encourage natural ventilation. The wind in Shenzhen
comes mostly from the east (southeast and northeast), so it is important
not to block the eastern side of the site. Our site design leaves
large openings to the east for the wind to enter. However, the
most recent plans for the site to the east show that several buildings
block the wind from entering our site. We encourage the designers
to create openings in these buildings to allow the wind to pass
into our site.

Western side of the site is partially open to allow
air into the adjacent site
Our site should not block the wind from the
future apartments to the west, so our design has several openings
in the west side. Ideally, for greater natural indoor ventilation,
the western buildings would not have openings to the next site,
but we must think of the future buildings.
Building Façades
Exterior color
The color of the exterior walls has minimal
impact (<1%) on the annual energy use (comparing red brick with
white paint). Therefore, the aesthetics of the color scheme is
more important than the energy.
nfiltration Infiltration
accounts for approximately 15% of the
total cooling energy load for a Base Case apartment (Base
Case is defined above). Construction and detailing techniques
should ensure that infiltration is less than 0.35 air changes per
hour in each apartment. All joints (windows, doors, fans) and cracks
should be sealed thoroughly to reduce leaks. (Use blower door test
on a random sample of apartments to ensure that they meet requirements).
Natural and fan-assisted ventilation
will provide fresh air. Providing ventilation at the proper times
(when the outside air is cooler than the cooling set-point temperature)
saves energy, rather than infiltration letting air in at all times.
To ensure good indoor air quality during the summertime (when air-conditioners
are used and windows are closed) occupants should ventilate for a
few minutes each morning using the exhaust fan.
Roof
Must be insulated with at least R=3.67 K*m2/W
(for example, 14cm of typical fiberglass or comparable insulation
inside the weather barrier). While providing only <100kWh (<3%)
of energy savings over the year, this improvement will keep the top-level
apartments more comfortable year-round.
Solar hot water collectors could provide
domestic hot water to many apartments (if not all) while removing
excess heat from the rooftop (thus making rooftop units more comfortable).
Solar hot water collectors, if used, should be integrated architecturally
with the roof to avoid bad aesthetics. The roof pitch in most designs
has been set at 22° toward the south because this is
the optimum incline to collect the sun throughout the entire year.
(To fully maximize the roof for solar hot water, designers could turn
the roof into a single-slope facing south with a 22 inclination, instead
of a double slope as it is currently with half sloping south and half
sloping north.) Solar hot water heaters
use direct sun radiation to collect heat and transfer it to water
for use in the home. Several designs exist ranging from glass plate
collectors, to evacuated tube solar collectors. They can be custom
built and integrated into a roof structure or pre-made in a factory
and installed on the roof after construction. The
U.S. Department of Energy states that every 1m2 of solar
collector area on a roof will heat roughly 40 liters of water/day
throughout the year in a southern climate (average throughout the
year). We believe that solar hot water heaters installed on every
roof would create a more sustainable building, although it may only
supply a portion of the total hot water demand. The solar water heaters
also remove heat from the roof area, leaving top-floor apartments
more comfortable. We provide you with some contact and reference
information on solar hot water heaters and ask that you fully investigate
this option.

U.S. Department of
Energy Gives an overview of
solar hot water technology
www.eren.doe.gov/femp/techassist/solar_water.html
Tsinghua Solar Co.
Produces evacuated tube
solar collectors in China
(background report ==>
http://www.usembassy-china.org.cn/english/sandt/chihotwt.htm)
thesolar@public.bta.net.cn
(Research and Development Division)
North Face Northern
windows should have small overhangs and fins. Although shading
the northern window does not have a large impact on energy savings
(<1% annually) it will greatly improve comfort during the summer
months when the sun is to the north. We recommend an overhang that
has a depth equal to 10% of the window height and fins with depths
equal to 10% of the window width. This shading plan will block 100%
of direct sunlight from August to April (obviously), 70% in May and
September, and 50% in June.
The Solar Heat Gain Coefficient
(SHGC) of the windows should be 0.8 or less (for example, 1/8
single pane, non-coated glass). Windows should have vinyl (plastic)
frames if possible to provide better heat insulation.
Windows adjacent to the railroad
tracks should have tightly sealing gaskets. If possible, these
windows should be non-operable (to eliminate air gaps) and should
have thick glass (at least 1/4 thick each pane). The most important
consideration is to eliminate air-gaps. (For example, a one square
meter window with a transmission loss of 30dB that has a 1mm x 1m
air-gap now has a transmission loss of 26dB; a 1cm x 1m gap produces
an equivalent T.L. of 19dB!)
|
Window Type
|
Transmission Loss (dB @ 500Hz)
|
|
Single pane (1/8 glass with gasket seal)
|
28
|
|
Single pane (1/4 glass with gasket seal)
|
31
|
|
Single pane (1/2 glass with gasket seal)
|
36
|
Exterior doors adjacent to the railroad tracks
should be heavy (such as metal with foam core, or 100% solid wood),
and should have gasket seals around the door and weather stripping
at the bottom of the door. This precaution will help reduce train
noise inside. Again, eliminating air-gaps is crucial.
|
Door Type
|
Transmission Loss (dB @ 500Hz)
|
|
Hollow-core metal (no gaskets)
|
16
|
|
Solid-core wood (no gaskets)
|
26
|
|
Solid-core wood (with foam gaskets)
|
30
|
Increase the mass of exterior
walls for buildings adjacent to the railroad tracks to help
reduce noise inside (e.g. fill concrete blocks with denser concrete)
South Face Southern
windows should have overhangs and fins. Shading the southern
window has a large impact on energy savings. We recommend an overhang
that has a depth equal to 20% of the window height and fins with depths
equal to 10% of the window width. This shading plan will block 100%
of direct sunlight from April through August, 60% in March and September,
40% in February and October, and 30% from November through January.
The Solar Heat Gain Coefficient
(SHGC) of the windows should be 0.8 or less (for example, 1/8
single pane, non-coated glass). Windows should have vinyl (plastic)
frames if possible to provide better heat insulation.
East Face Western
and eastern windows must be self-shaded to block
late-day and early-morning sunlight. Overhangs and fins are ineffective
because of the sun angles are so low in the morning and afternoon.
Therefore, the Solar Heat Gain Coefficient (SHGC) of the window itself
must be less than 0.4. (The total solar radiation transmitted and
re-radiated by a window [q] equals the total solar radiation hitting
the exterior of the window [E] times the SHGC), or:
[Watts]
We propose two methods for achieving a SHGC
of less than 0.4 on eastern and western windows. The first method
uses high-quality, double pane windows that do not obstruct the
view from inside. The second method uses an exterior screen (similar
to an insect screen) mounted on a standard single-pane window.
The following details both methods:
Method 1 (Advanced Windows):
A double pane, low-emmitance (low-e) window
can achieve a SHGC less than 0.4. The e-value must be 0.05 or less.
A single pane tinted window may also achieve a SHGC less than 0.4.
Check with individual window manufacturers in China to find window
performance.
Method 2 (Exterior Screens):
Exterior screens, such as the ones produced
by Phifer Wire Products, Inc. in the U.S. and exported to World
Choice Asia Limited in Hong Kong, combined with a single-pane window
will produce a SHGC of less than 0.4. Phifers SunScreen
and ShadeScreen products are two that provide adequate
sun protection.
Phifer Wire Products, Inc.
Produces the sun-screen products (just the
fabric)
P.O. Box 1700
Tuscaloosa, AL 35403-1700
USA
Tel: 205-345-2120
www.phifer.com
World Choice Asia, Ltd.
Imports Phifer products and makes them into
shading devices
Rm.1212, Metro Centre II
21 Lam Hing Street
Kowloon Bay
Kowloon West Face
Should have R=1.5 K*m2/W or greater
(for example, block wall with 6cm of glass fiber insulation inside
the weather barrier). This will help keep the western facing apartments
cooler late in the day during summertime. Although this increases
the comfort of occupants late in the day during the warmest months,
it does not save much energy over the entire year (<1%)?
Ventilation
>Proper ventilation during spring and fall can
save up to 30% in annual energy usage if used at the correct times.
Wind driven ventilation alone will give
between 0 and ~30 air changes per hour (ACH), depending on the apartments
location and the direction of the wind, during spring and fall.
ACH for select apartments (East Wind- 3 m/s)
|
Apt. #
|
Delta P (Pa)
|
Q (m3/s)
|
ACH |
|
1
|
0.0
|
0.00
|
<1
|
|
2
|
0.7
|
0.38
|
13
|
|
3
|
3.0
|
0.79
|
28
|
|
4
|
0.3
|
0.25
|
9
|
|
5
|
0.3
|
0.25
|
11
|
|
6
|
0.0
|
0.00
|
<1
|
|
7
|
2.0
|
0.65
|
23
|
|
8
|
0.7
|
0.38
|
10
|
|
9
|
1.0
|
0.46
|
16
|
|
10
|
0.7
|
0.38
|
14
|
|
11
|
0.3
|
0.25
|
11
|
|
12
|
0.0
|
0.0
|
0.0
|
|
13
|
0.0
|
0.0
|
0.0
|
|
14
|
0.0
|
0.0
|
0.0
|
Natural ventilation is an essential tool for
an energy-efficient apartment. Unfortunately, wind is often unreliable
and adjacent buildings block some of the wind when it does blow.
Therefore, we suggest installing exhaust fans in each apartment
to limit the need for air-conditioning when wind alone does not
produce enough natural ventilation.
Large exhaust fans (similar to
kitchen and bathroom fans, but larger) should be installed in each
apartment to provide an average hourly air change rate of 36 (for
a 100m2 x 3m apartment, that means 3m3/s through
the fan). The required flow rate is calculated for cooling a typical
apartment (H2) with a total cooling load of 55.5 Watts/m2
to within 2°C of the outdoor air temperature. The
cooling load was calculated as an average for the six months of
March May and September November. Assumed ideal mixing
where:


A typical exhaust fan must be about 0.5
0.7m in diameter to provide the required airflow rate for a pressure
loss of 150Pa (20 Pa static pressure). ACME Engineering and Manufacturing
Corporation in the U.S. makes a large line of such fans. We assume
similar manufacturers and products exist in China and are readily
available.
We suggest placing the exhaust fan in the kitchen
of most apartments for aesthetic reasons. On the northern row of
buildings near the railroad tracks, however, avoid placing fans
on the side exposed to the railroad because they will leak noise
into the apartments. For top floor apartments, we suggest placing
the fan in the wall near the top of the cathedral ceiling to expel
the hot air first. In most installations, and for most apartments,
the total static pressure loss is near 20Pa.
ACME Engineering & Manufacturing Corporation
P.O. Box 978
Muskogee, OK 74402
USA
Tel: 918-682-7791
Fax: 918-682-0134
www.acmefan.com
acmefan@acmefan.com
Noise
Noise is a noted concern for the comfort of
occupants in apartments adjacent to the railroad tracks. The northern
row of apartments is shielding the rest of the site from noise,
but it must also protect its own occupants from noise. All exterior
surfaces (at all heights) with an unobstructed view of the railroad
tracks (including buildings at the northwest corner) should heed
the following:
People expect noise privacy so that outside
noise infiltration is less than 35dBA in bedrooms, less than 40dBA
in living and dining rooms, and less than 45dBA in bathrooms and
kitchens.
Trains produce ~90dBA of noise (most train
noise is at low frequencies). A traffic barrier will give up
to 15dBA noise reduction, the distance away from the tracks (~20m)
will give 6dBA reduction, proper window/wall/door combination
(as discussed above) will give 20-40dB reduction when doors/windows
are closed. (Only 20dB reduction is possible if doors and windows
have gasket seals, and up to 40dB reduction is possible if all
noise recommendations are used.)

Acceptable indoor noise levels
Train noise spectrum
Thermostat It is extremely
important for the occupants to be aware of the temperature and humidity
indoors and out so they can operate the windows, fan, and air conditioner
efficiently. The user manual (attached at the end of this report)
guides occupants on how to use natural ventilation, mechanical ventilation,
and air-conditioning based on the temperature difference between indoors
and outdoors.
All the apartments should have digital, programmable,
clock-thermostats that monitor and display the indoor and outdoor
temperature.
Air Conditioner Occupants
should be encouraged to buy efficient air conditioners. The units
should have a minimum COP of 3 (COP = Heat Extracted / Electricity
Input). Based on a ten year payback, it is economical (and efficient)
for occupants to upgrade the unit by 0.3 COP each time the upgrade
costs less than 1500 yuan. (For example, they should buy a 3.9 COP
unit if it costs up to 4500 yuan more than the 3.0 COP unit; buy a
4.2 COP unit if it costs up to 6000 yuan more than the 3.0 COP unit.)
Air conditioners that have too much capacity
(Watts) run inefficiently. Since these apartments are designed
to use less energy than typical units in China, there is a risk
that air conditioner sellers may oversize the air conditioner (meaning
higher initial cost to the occupants, and more overall electricity
use). Energy calculations based on the above recommendations indicate
that air conditioners should be sized at ~100W/m2. (For
example, a 100m2 apartment should have 10kW of total
air conditioning capacity to meet peak summer demand.)
Shenzhen Residential User Manual
Building occupants should use this guide to
control their apartment for comfort and energy-efficiency. This
is a first draft of the manual, and it may change depending on which
energy-efficiency recommendations are implemented into the apartments.
The information here is a guide to obtain optimum energy-efficiency,
but may be altered according to personal preference and habits.
Use of thermostat to minimize energy use
The programmable thermostat allows the user
to come home or wake up in a comfortable home without conditioning
it while sleeping or away from the home. A thermostat, which monitors
indoor and outdoor conditions, and controls the heating, cooling,
and ventilation equipment for a home, can be used to turn the equipment
off even when the user is not at home. With the use of a programmable
digital thermostat, we recommended using the following temperature
settings throughout the year:
| |
Cooling Season
|
Mixed Season
|
Heating Season
|
|
Early Morning
|
26°C (30 if away)
|
Off (fans on)
|
22°C (20 if away)
|
|
Mid Morning
|
30°C (27 if home)
|
30°C (27 if home)
|
20°C (22 if home)
|
|
Mid Day
|
30°C (27 if home)
|
30°C (27 if home)
|
20°C (22 if home)
|
|
Mid Afternoon
|
30°C (27 if home)
|
30°C (27 if home)
|
20°C (22 if home)
|
|
Evening
|
26°C (30 if away)
|
27°C (30 if away)
|
20°C (22 if home)
|
|
Late Evening
|
27°C (30 if away)
|
Off (fans on)
|
22°C (20 if away)
|
You
may alter these settings to suit your comfort level (noting that
you may increase your energy use). Sometimes, high humidity will
force you to use air-conditioning even when the temperature outside
dictates natural ventilation (this is perfectly understandable).
Use of temperature readings to control air
conditioning and ventilation:
A user can optimize their air-conditioner and
fan use by using this chart and the temperature readings from the
indoor/outdoor thermostat:
|
Inside Temperature:
|
Outside Temperature:
|
User Action:
|
|
Above the cooling setpoint
|
At least 2°C below the cooling setpoint
|
Turn off A/C, use natural or mechanical ventilation.
|
|
Above the cooling setpoint
|
Above the cooling setpoint
|
Turn on A/C, turn off fan and close windows.
|
|
Below the cooling setpoint, above the heating setpoint
|
Below the cooling setpoint
|
Turn off A/C, use natural or mechanical ventilation.
|
|
Below the cooling setpoint, above the heating setpoint
|
Above the cooling setpoint
|
Turn off A/C and fan and close windows.
|
|
Below the heating setpoint
|
Below the heating setpoint
|
Turn off A/C and fan and close windows.
|
|
Below the heating setpoint
|
Above the heating setpoint
|
Turn off A/C, use natural or mechanical ventilation.
|
During the hottest months, when using the air-conditioner
all day and not opening the windows (because it is too hot and humid
outside), occupants should ventilate the apartment for 5 minutes
every morning to ensure good indoor air quality. Occupants may
also choose to ventilate the apartment in the evening (before bedtime)
for 5 minutes if the air seems stale. To ventilate during these
times, occupants should open all the windows and interior doors,
then turn the exhaust fan on (full speed) for five full minutes.
After ventilating, occupants should close all windows and use the
air conditioner to bring the indoor temperature back to the cooling
set-point. Note: The above ventilating procedure is only necessary
when the outdoor temperature/humidity is too high for natural ventilation
(i.e. when the windows have been closed all day).
Use of shading devices to minimize heat gain
from the Sun:
To minimize the heat gain from the sun, the
residence should have the blinds or other shading devices covering
the windows while the sunlight is in direct contact with the window.
Leaving the windows covered throughout the entire day while the
resident is not home will make the home more comfortable toward
the end of the day, as compared to allowing the sunlight to enter
the residence. Blinds or shades should even be used if the window
is opened (sunlight can be blocked while still letting air in for
natural ventilation).
Use of natural ventilation or mechanical
ventilation to remove hot air:
You should open windows and interior doors so
wind will move hot air out of the apartment and make your home comfortable.
During the spring and fall, you may be able to use natural ventilation
all day without needing an air-conditioner. During the warmer months,
you may only be able to use ventilation during nighttime or morning
hours (or not at all). Use an indoor/outdoor thermostat (as described
above) to determine when ventilation will make your apartment more
comfortable. If it is uncomfortable inside,
but the indoor/outdoor thermostat says you can use natural ventilation,
then the wind may not be strong enough and you should turn the exhaust
fan on. When the fan is on, you should still have your windows
and interior doors open to allow the air to pass through.
back to top
|