|
Indoor Airflow Analysis of Duplex and
Single Apartment within Shanghai Building
Camille Alloca
A CFD analysis was performed on indoor
airflow within a duplex and single apartment in Shanghai,
China, with the intent of maximizing natural ventilation through
the building. To perform the indoor airflow analysis, architectural
floor plans and unit layouts, as well as window placement
and size, were provided for each apartment. The assumptions
made and results reported for this analysis are outlined in
this paper.
>INDOOR ENVIRONMENT SETUP
In the CFD simulation of the indoor
environment, the following parameters were solved for and
analyzed: pressure (p), velocity (v), temperature (T), CO2
concentration (c), humidity ratio (w), relative humidity (f),
percentage of persons dissatisfied (PPD), persons dissatisfied
due to draft (PD), ventilation effectiveness (h),
and age of air (t). In order to solve these
parameters, input values had to be chosen based on reasonable
conditions. These input parameters, chosen for both the duplex
and single apartment CFD simulation, are shown in Table 1. The CFD simulation
for both apartments used the Renormalization group (RNG) k-e
turbulence model.
Table 1:
Input parameters for CFD simulation of duplex and single apartments
|
Input parameters
|
Inlet Value
|
Source Value
|
|
Temperature/
Heat Flux
|
T
|
24 °C
|
Occupant**
|
100 W
|
|
Television
|
300 W
|
|
Refrigerator
|
400 W
|
|
Pressure
|
p
|
*
|
-
|
|
Humidity Ratio
|
w
|
13
g water/kg air
|
Occupant**
|
55
g water/hour
|
|
Relative Humidity
|
f
|
70%
|
-
|
|
CO2 concentration
|
c
|
400 ppm
|
Occupant**
|
5 mL/s
|
|
Age of Air
|
t
|
0
|
1 (everywhere)
|
|
|
|
|
|
|
* Both inlet and outlet pressures
were input and vary between the duplex and single apartment.
**Values refer to each
of the 4 occupants.
DUPLEX APARTMENT
SINGLE APARTMENT
The floor plan of the
single apartment chosen for this analysis is shown in Figure
1. The apartment consists of an open area, kitchen,
bathroom, and three bedrooms (8 m x 14.8 m x 2.8 m). The
layout set up in the CFD program, PHOENICS, is shown in Figure
2. In order to model the physical environment of this
apartment, certain assumptions had to be made within the CFD
program. A southeast section of the apartment was not part
of the apartment, and was therefore modeled as a blockage
(see Figure
1). Minimum furnishings within the apartment were
modeled by placing a bed and closet in each bedroom, and a
table in the living room. This was done in order to get a
rough idea of how blockages within the apartment effected
the airflow patterns. A 49 x 82 x 17 grid was set up, providing
a fine mesh.

Figure 1:
Single apartment layout

Figure 2:
Single apartment modeled in CFD
The single apartment is fully exposed
on the south, east, and north side and partially exposed at
the northern corner of the west side, as shown in Figure 2. Given this exposure,
an optimum window layout design was chosen. Since the apartment
layout consisted of many partitions parallel to the south
facade (where the wind was directed), it was necessary to
maximize the openings on all facades to obtain good cross
ventilation. Therefore, either one or two windows were placed
in each room (see Figure 1). Each window was
assumed to be 1m x 1m, but was simulated as being open halfway,
or 0.5 m wide x 1 m high.
Windows were modeled as fixed-pressure
outlets. Pressures for each side of the building were obtained
from the outdoor airflow analysis around a sealed building.
This outdoor analysis assumed a velocity of 2 m/s approaching
the building site from the south. For the indoor analysis
discussed in this paper, outdoor pressures were taken at a
height in the center of the building, or 18.2 m. The pressures
obtained from this analysis are shown in Table 2 for each window.
There was an uncertainty inherent in the exact location of
extracting these outdoor pressures from the outdoor flow simulation
that must be considered.
Table 2:
Outdoor pressures at windows for z=18.2 m
|
Room
|
Window
Orientation
|
Pressure (Pa)
|
|
kitchen
|
north
|
-0.650
|
|
north bedroom
|
north
|
0.008
|
|
east
|
1.983
|
|
center bedroom
|
east
|
3.769
|
|
south
|
7.215
|
|
south bedroom
|
east
|
7.215
|
|
living room
|
east
|
7.055
|
|
south
|
7.430
|
In order to determine
the potential for natural ventilation within this apartment,
the velocity profile was evaluated at a suitable height
of 1.5 m within the occupied zone. Velocity contours and
vectors are shown in Figure
3.

Figure 3:
(a) Velocity vectors and (b) contours at z=1.5 m
For the single apartment, the airflow
enters through both south-facing windows and two east-facing
windows, as shown in Figure
3a. This airflow created high ventilation rates through
the hallway and through the entrance to the north bedroom
and kitchen, where the air then exited the building at high
velocities. The air change rate at a building height of 18.2
m was calculated as

This air change rate allows for good natural
ventilation through the building. The design was therefore
found to be satisfactory. However, areas of low velocity
in the center and south bedroom, ranging from 0.01 to 0.1
m/s, may not provide sufficient natural cooling. There are
also areas of extremely high air velocities through the hallway,
north bedroom and kitchen, which may contribute to discomfort
due to draft, as will be discussed later. These areas of
extreme low and high airflow within the single apartment still
need to be addressed further.
The temperature values were mostly
constant throughout the single apartment. Values for temperature
were found to be about 24 °C in most of the space,
with temperature reaching only 25 °C in those
areas where heat sources were located.

Figure 4:
Temperature contours at z=1.5 m
The thermal comfort parameters calculated
in the CFD simulation were percentage of persons dissatisfied
(PPD), persons dissatisfied due to draft (PD), relative humidity
(f), ventilation effectiveness (h),
and age of air (t). The PPD calculated for the
single apartment is shown in Figure
5. For most of the space in the apartment, a PPD was
calculated between 5-6%. However, there were areas within
the apartment that reached PPD values of up to 30% and should
therefore be of concern. A similar trend to that of PPD was
found when calculating PD, except the fact that PD spanned
over a larger range of values, from 0 100% (Figure
6). Areas of greatest concern are those with high
airflows: the hallway and entrance to the north bedroom and
kitchen. These locations contain PD values ranging from 40%
to 100%.
The relative humidity (f)
was calculated as a function of the temperature and humidity
ratio (w) at a particular location. Therefore, inlet and
source humidity ratio values were input into the CFD simulation
in order to calculate the relative humidity. The range of
values for f were found to be between 70
74% (Figure
7). The ventilation effectiveness (h)
was then calculated as a function of the inlet, outlet, and
source concentration (c). Therefore, inlet and source CO2
concentration values were input into the CFD simulation in
order to calculate h (see Table
1). The range of values for h was found
to be between 20-100% (Figure
8). However, most of the space was characterized by
h=100%. Finally, the age of air (t)
was calculated by assuming a unit source at every location
in the room and t=0 at the inlets. This produced
results for t ranging from 0 102 s (Figure
9). The age of air for complete mixing was determined
to be:

which is within the calculated range for
t. The CFD calculation for h and
t seems to show good mixing, without any areas
of stagnant air.
An overview of the range of values
found for the various parameters solved is shown in Table 3.

Figure 5:
PD contours at z=1.5 m

Figure 6:
PPD contours at z=1.5 m

Figure 7:
Relative humidity contours at z=1.5 m

Figure 8:
Ventilation effectiveness contours at z=1.5 m

Figure 9:
Age of air contours at z=1.5 m
Table 3: Solved parameters for CFD simulation of single
apartment
|
Solved Parameter
|
Range of Values
|
|
Temperature
|
T
|
24-25 °C
|
|
Velocity
|
v
|
0.01-1.2 m/s
|
|
Pressure
|
p
|
3-5 Pa
|
|
Percentage of Persons Dissatisfied
|
PPD
|
5-30%
|
|
Persons Dissatisfied due to Draft
|
PD
|
0-100%
|
|
Humidity Ratio
|
w
|
13-14.5 g water/kg air
|
|
Relative Humidity
|
f
|
70-75%
|
|
CO2 concentration
|
c
|
400-500 ppm
|
|
Ventilation Effectiveness
|
h
|
20-100%
|
|
Age of Air
|
t
|
0-102 s
|
AIR CHANGE RATES ALONG BUILDING HEIGHT
In order to determine the effect of pressure
changes along the height of the building on indoor airflow
rates, CFD simulations were run at 3 m intervals in height
for both the duplex and single apartment. By extracting data
from the outdoor flow simulation, outdoor pressure was plotted
as a function of height at each of the openings. At each
interval in height, the appropriate outdoor pressure value
was extracted for each opening and the CFD simulation was
run in order to determine the ACH.
For the single apartment calculation,
outdoor pressures were extracted at each of the 8 openings
as a function of height. After running the CFD simulation
at 6 vertical locations, the ACH in the single apartment was
determined as a function of height, as shown in Figure 10.
This analysis allows for interpolation of airflow rates in
the single apartment at all 12 stories of the building.

Figure 10:
ACH versus height for the single apartment
back to top
|