|
Analysis
of Summer Heat Removal in the "12x12 units", Beijing
Guilherme
Carriho-da-Graca, MIT Building Technology Program, gcg@mit.edu
March
11, 1999
Below a simple analysis of stack effect ventilation
for a six story housing unit is presented. Air change rates are
calculated as well as predicted temperature increase between the
inlet and outlet. A comparison of the pressure generated by wind
the stack is also presented.
In the figure on the right we can see a representation
of the way the building is being modeled. Apertures only exist in
the upper and lower floor and the internal; resistances are neglected.
The internal flow resistances are neglected. The lower and the upper
floor have the same opening area. Once the air enters a unit it
is considered to suffer total mixing and an immediate increase in
temperature due to the internal gains. In the charts presented below
the number of units is a parameter, when a lower number of units
is considered the lower aperture is placed in the lowest unit and
the higher in the highest unit.
The values proposed by ASHRAE were used for
estimating the internal gains. Due to the fact that we are studying
apartment units we use a metabolic rate for each occupant of 1.2
met , which for an exposed area of 1.2 m2 gives a heat gain of 85
W per occupant. Each unit is considered to have five occupants.
The machine and appliances heat gains are considered to be 470 W
(single family house). Therefore for each of the units we have:
Total Gains=470+5x85=895 W
The ceiling height used for each floor is 2.5m.

To calculate the static pressure loss when the
flow passes through the openings in the façade the aperture equation
was used (with a discharge coefficient of 0.65).
Figure
1, Aperture configuration.
Results

Figure 2
Temperature
increase of the air as in each unit, for a range o aperture areas.
Upper curve is for two stories, lower curve is for six stories.

Figure 3
Air
changes per hour in each building, for a range of aperture areas.Upper
curve is for two stories, lower curve is for six stories.

Figure
4.1
Comparison
between the stack generated pressure and the wind generated pressure
at the outlet (see blue arrow in figure 1) for a two stories building.
The aperture area used for the calculation of the required heat
gains per unit (horizontal axis) was 1.5 m^2. The wind velocity
used was 1.5 m/s.

Figure
4.2
Comparison
between the stack generated pressure and the wind generated pressure
at the outlet (see blue arrow in figure 1) for a three stories building.
The aperture area used for the calculation of the required heat
gains per unit (horizontal axis) was 1.5 m^2. The wind velocity
used was 1.5 m/s.

Figure 4.3
Comparison
between the stack generated pressure and the wind generated pressure
at the outlet (see blue arrow in figure 1) for a four stories building.
The aperture area used for the calculation of the required heat
gains per unit (horizontal axis) was 1.5 m^2. The wind velocity
used was 1.5 m/s.

Figure 4.4
Comparison
between the stack generated pressure and the wind generated pressure
at the outlet (see blue arrow in figure 1) for a five stories building.
The aperture area used for the calculation of the required heat
gains per unit (horizontal axis) was 1.5 m^2. The wind velocity
used was 1.5 m/s.

Figure 4.5
Comparison between the stack generated pressure
and the wind generated pressure at the outlet (see blue arrow in
figure 1) for a six stories building. The aperture area used for
the calculation of the required heat gains per unit (horizontal
axis) was 1.5 m^2. The wind velocity used was 1.5 m/s.
Comments on the results:
Figure 2 shows as expected that the smaller
the area the smaller the flow rate. Since the heat to be removed
is constant (the internal gains) the temperature difference between
the inlet and the outlet air is inversely proportional to the aperture
areas. Note that, for example, when five units are considered the
internal gains are only from the five units (that is the reason
why the temperature difference decreases with the number of units).
Figure 3, in this chart it is important to note
that the air change rate is for the whole building.
Figure 4, In this figure we compare the stack
pressure with the wind pressure at the outlet (see blue arrow in
figure 1, we are comparing the pressure generated by wind that comes
from left to right, generating a pressure that works against the
stack effect).
Pstack depends on the square root of the internal
gains, therefore the ratio:
Pstack/Pwind increases with the internal gains.
Whenever Pstack>Pwind the stack will still
remove the internal gains (although with the wind pressure working
against the stack the building will heat up because the air change
rate will decrease).
back to top
|